Goto Section: 68.300 | 68.304 | Table of Contents
FCC 68.302
Revised as of
Goto Year:1996 |
1998
Sec. 68.302 Environment simulation.
Registered terminal equipment and registered protective circuitry
shall comply with all the criteria contained in the rules and
regulations in this subpart, both prior to and after the application of
each of the mechanical and electrical stresses specified in this
section, not withstanding that certain of these stresses may result in
partial or total destruction of equipment.
(a) Vibration. The equipment shall be subjected to vibration while
in the condition that it is normally shipped or transported. That is,
during the following vibration test the equipment shall be vibrated
while packaged if shipped packaged, or the equipment shall be vibrated
while unpackaged if shipped unpackaged. The following sinusoidal
vibration should be applied once in each of three orthogonal directions,
however, for large equipments, the unit should rest on the base or side
on which it is normally shipped: One sweep at a level of 0.5g peak from
5 to 100 Hz, and one sweep at a level of 1.5g peak from 100 to 500 Hz.
The 5 to 100 Hz sweep should be conducted at a sweep rate of 0.1 octave/
min. (approximately 45 minutes) and the 100 to 500 Hz sweep at a rate of
0.25 octave/min. (approximately 10 minutes).
(b) Temperature and humidity. Cycling at any convenient rate through
the following temperature and humidity conditions three times: 30
minutes at 65 deg. C (150 deg. F) and 15 percent relative humidity,
followed by 30 minutes at 32 deg. C (90 deg. F) and 90 percent relative
humidity, followed by 30 minutes at -40 deg. C (-40 deg. F) and any
convenient humidity.
(c) Shock. (1) Registered Terminal Equipment and Registered
Protective Circuitry Equipment Unpackaged:
Hand-Held Items Normally Used at Head Height:
18 random drops from a height of 150 cm (60 in) onto concrete
covered with 3 mm (\1/8\ in) asphalt tile or similar surface.
Normally Customer Carried Equipment:
6 random drops from a height of 75 cm (30 in) onto concrete covered
with 3 mm (\1/8\ in) asphalt tile or similar surface.
Equipment Not Normally Customer Carried:
These tests are made onto concrete covered with 3 mm (\1/8\ in)
asphalt tile or similar surface.
0-10 kg (0-20 lbs): One 15 cm (6 in) face drop on each normal or
designated rest face, one 7 cm (3 in) drop on all other faces, and one 7
cm (3 in) corner drop on each corner.
10-20 kg (20-50 lbs): One 10 cm (4 in) face drop on each normal or
designated rest face, one 5 cm (2 in) face drop on all other faces, and
one 5 cm (2 in) corner drop on each corner.
20-50 kg (50-100 lbs): One 5 cm (2 in) face drop on each normal or
designated rest face. One edgewise drop and one cornerwise drop from a
height of 5 cm (2 in) on each edge and corner adjacent to the rest face.
50-500 kg (100-1000 lbs): One 2 cm (1 in) face drop on each normal
or designated rest face. One edgewise drop and one cornerwise drop from
a height of 2 cm (1 in) on each edge and corner adjacent to the rest
face.
Over 500 kg (1,000 lbs): One 2 cm (1 in) face drop on each normal or
designated rest face. One edgewise drop from a height of 2 cm (1 in) on
each edge adjacent to this rest face.
(2) The drop tests specified in the mechanical shock conditioning
stresses shall be performed as follows:
FACE DROP--The unit should be dropped such that the face to be
struck is approximately parallel to the impact surface.
CORNER DROP--The unit should be dropped such that upon impact a line
from the struck corner to the center of gravity of the packaged
equipment is approximately perpendicular to the impact surface.
EDGEWISE DROP--The unit should be positioned on a flat test surface.
One edge of the rest face should be supported with a block so that the
rest face makes an angle of 20 deg. with the horizontal. The opposite
edge should be lifted the designated height above the test surface and
dropped.
CORNERWISE DROP--The unit should be positioned on a flat test
surface. One corner of the test face should be supported with a block so
that the rest face makes an angle of 20 deg. with the horizontal. The
opposite corner should be lifted the designated height above the test
surface and dropped.
RANDOM DROP--The unit should be positioned prior to release to
ensure as nearly as possible that for every six drops there is one
impact on each of the six major surfaces and that the surface to be
struck is approximately parallel to the impact surface.
(d) Metallic voltage surge. Two 800-volt peak surges of a metallic
voltage (one
[[Page 275]]
of each polarity) having a 10-microsecond maximum rise time to crest and
a 560-microsecond minimum decay time to half crest applied between (1)
tip and ring of a 2-wire connection; (2) between tip and ring, and tip 1
and ring 1 of a 4-wire connection; (3) between tip and tip 1 (with tip
and ring tied together and tip 1 and ring 1 tied together) of a 4-wire
connection which uses simplexed pairs for signaling; and (4) any other
pair of connections on which lightning surges may occur (with one of the
connections of the pair under test grounded) with the equipment in each
of the following states:
(i) Any operational state which can affect compliance with the
requirements of part 68;
(ii) Any state in which the equipment might be connected to the
telephone network and from which it is capable of transferring to an
operational state by an automatic or manual action required for proper
use of the equipment and provided that any such state can affect
compliance with the requirements of part 68; and
(iii) Any state in which the equipment might be connected to the
telephone network through an automatic or manual action under all
reasonably foreseeable possibilities of disconnection of connections of
such equipment with primary commercial power sources (including possible
loss of equipment grounding through disconnection of a third-wire ground
connection contained in a primary power source plug).
All other equipment leads (telephone connections, auxiliary leads, and
terminals for connection to nonregistered equipment) not being surged or
connected to those being surged should be terminated in a manner which
is no less severe than that which occur in normal use and affect
compliance with subpart D. Also, equipment states which cannot be
achieved by normal means of power shall be achieved artificially by
appropriate means, if necessary to comply with the above requirements.
The peak current drawn from the surge generator must not be limited to
less than 100 amperes by the capabilities of the surge generator except
for the simplexed arrangement in case (3), which must not be limited to
less than 200 amperes.
(e) Longitudinal voltage surge. With registered terminal equipment
in each of the following states: first, any operational state which can
affect compliance with the requirements of part 68, second, any state in
which the equipment might be connected to the telephone network and from
which it is capable of transferring to an operational state by an
automatic or manual action required for proper use of the equipment and
provided that each state can affect compliance with the requirements of
part 68 and third, any state in which the equipment might be connected
to the telephone network through an automatic or manual action under all
reasonably foreseeable possibilities of disconnection of connections of
such equipment with primary commercial power sources (including possible
loss of equipment grounding through disconnection of a third-wire ground
connection contained in a primary power source plug):
(1) Two 1500 volt peak surges (one of each polarity) having a 10
microsecond maximum rise time to crest and a 160 microsecond minimum
decay time to half crest applied separately between each of the
following leads individually and (i) and (ii) below, and where
available, also between all of the following leads tied together and (i)
and (ii) below: Tip, ring, tip 1, ring 1, M (only for registered
terminal equipment located on the ``A'' side of a Type I E&M interface).
(i) Earth ground; and
(ii) All leads on the registered equipment intended for connection
to non-registered equipment when these leads are connected together.
The peak current drawn from the surge generator must not be limited to
less than 200 amperes by the capabilities of the surge generator.
(2) Two 1500 volt peak surges (one of each polarity) having a 10
microsecond maximum rise time to crest and a 160 microsecond minimum
decay time to half crest applied between pairs of connections other than
tip and ring on which lightning surges may occur, connected together,
and individually to (i) and (ii) below:
(i) Earth ground; and
[[Page 276]]
(ii) All leads on the registered equipment intended for connection
to non-registered equipment when these leads are tied together.
The peak current drawn from the surge generator shall not be limited to
less than 200 amperes by the capabilities of the surge generator.
(3) Six 2500 volt peak surges (three of each polarity) having a 2
microsecond maximum rise time to crest and a 10 microsecond minimum
decay time to half crest applied between the phase and neutral terminals
of the ac power line. The peak current drawn from the surge generator
must not be limited to less than 1000 amperes by the capabilities of the
surge generator.
All other equipment leads (telephone connections, auxiliary leads, and
terminals for connection to non-registered equipment) not being surged
or connected to those being surged should be terminated in a manner
which is no less severe than that which would occur in normal use and
affect compliance with subpart D. Also, equipment states which cannot be
achieved by normal means of power shall be achieved artificially by
appropriate means, if necessary to comply with the above requirements.
(f) Failure modes resulting from the application of metallic and
longitudinal surges. Registered terminal equipment and registered
protective circuitry are permitted to reach a failure-mode state in
violation of longitudinal balance requirements of Sec. 68.310, and for
terminal equipment connected to Local Area Data Channels a failure-mode
state in violation of the longitudinal signal power requirements of
Sec. 68.308, after application of the electrical surges specified in
paragraphs (d) and (e) herein, provided that:
(1) Such failure results from an intentional, designed failure mode
which has the effect of connecting telephone or auxiliary connections
with earth ground; and,
(2) If such a failure-mode state is reached, the equipment is
designed in such a manner that it would become substantially and
noticeably unusable by the user, or an indication is given to the user
(e.g., an alarm), in order that such equipment can be immediately
disconnected or repaired.
Note: The objective of this subsection is to allow for safety
circuitry which diverts lightning-like transients to earth ground, but
which may continue to maintain the earth ground connections after the
transients have ceased. Such a failure-mode has the potential for
causing interference resulting from longitudinal imbalance, and
therefore designs must be adopted which will cause the equipment either
to be disconnected or repaired rapidly after such a state is reached,
should it occur in service. This subsection does not apply to tie trunk
interface leads.
[ 45 FR 20853 , Mar. 31, 1980, as amended at 50 FR 47549 , Nov. 19, 1985;
51 FR 944 , Jan. 9, 1986; 51 FR 16689 , May 6, 1986; 58 FR 44907 , Aug. 25,
1993]
Goto Section: 68.300 | 68.304
Goto Year: 1996 |
1998
CiteFind - See documents on FCC website that
cite this rule
Want to support this service?
Thanks!
Report errors in
this rule. Since these rules are converted to HTML by machine, it's possible errors have been made. Please
help us improve these rules by clicking the Report FCC Rule Errors link to report an error.
hallikainen.com
Helping make public information public