Goto Section: 68.310 | 68.314 | Table of Contents

FCC 68.312
Revised as of
Goto Year:1996 | 1998
Sec. 68.312  On-hook impedance limitations.

    (a) General. The limitations in this section that involve 2-wire 
network ports apply to tip and ring of the public switched network. For 
4-wire network ports (tip, ring, tip 1, and ring 1) with loop-start or 
ground-start signaling, the limitations apply when tip and ring 
conductors are connected together and treated as one of the conductors 
of a tip and ring pair and the tip 1 and ring 1 conductors are connected 
together and treated as the other conductor of a tip and ring pair.
    (b) Limitations on individual equipment intended for operation on 
loop-start telephone facilities, including PSDS Type II in the analog 
mode:
    (1) Registered terminal equipment and registered protective 
circuitry shall conform to the following limitations, for each Ringing 
Type which is listed as part of its Ringer Equivalence:
    (i) The dc resistance between tip and ring conductors, and between 
each of the tip and ring conductors and earth ground, shall be greater 
than 5 megohms for all dc voltages up to and including 100 volts.
    (ii) The dc resistance between tip and ring conductors, and between 
each of the tip and ring conductors and earth ground shall be greater 
than 30 kilohms for all dc voltages between 100 and 200 volts.
    (iii) During the application of simulated ringing, as listed in 
table I below, the total dc current, shall not exceed 3.0 milliamperes.

[[Page 306]]

    (iv) During the application of simulated ringing, as listed in table 
I below, the impedance between the tip and ring conductors (defined as 
the quotient of applied ac voltage divided by resulting true rms 
current) shall be greater than the value specified in table I. Except as 
provided in paragraph (b)(2) of this section, such impedance shall be 
less than 40 kilohms.
    (v) During the application of simulated ringing, as listed in table 
I below, the impedance between each of the tip and ring conductors and 
ground shall be greater than 100 kilohms.
    (2) Registered terminal equipment and registered protective 
circuitry intended for use on facilities which will always have ringing 
detection circuitry in use at the same time such registered terminal 
equipment and registered protective circuitry is connected need not 
comply with the 40 kilohms maximum impedance specification of paragraph 
(b)(1)(v) of this section.
    (c) Limitations on individual equipment intended for operation on 
ground-start telephone facilities. Registered terminal equipment and 
registered protective circuitry shall conform to the following 
limitations for each Ringing Type which is listed as part of its Ringer 
Equivalence Number:
    (1) During the application of simulated ringing, as listed in table 
I below, the total dc current flowing between tip and ring conductors 
shall not exceed 3.0 milliamperes.
    (2) During the application of simulated ringing, as listed in table 
I below, the total impedance of the parallel combination of the ac 
impedance across tip and ring conductors and the ac impedance from the 
ring conductor to ground (with ground on the tip conductor) shall be 
greater than the value specified in table I. Except as provided in 
paragraph (b)(2) of this section, such impedance shall be less the 40 
kilohms.
    (d) Ringer equivalence definition. The values of each of the 
parameters for which a limitation is imposed in paragraph (b) or (c) of 
this section, as appropriate, shall be determined for a representative 
unit under test. Quotients of each such value shall be formed according 
to the following:
    (1) For individual equipment intended for operation on loop-start 
telephone facilities:
    (i) 25 megohms divided by the minimum measured on-hook dc resistance 
for all dc voltages up to and including 100 volts.
    (ii) 150 kilohms divided by the minimum measured on-hook dc 
resistance for all dc voltages between 100 and 200 volts.
    (iii) The maximum total dc current flowing between tip and ring 
during the application of simulated ringing as listed in table I below, 
in milliamperes, divided by 0.6 milliamperes.
    (iv) Five times the impedance limitation listed in table I, below, 
divided by the minimum measured ac impedance, defined as in paragraph 
(b)(1)(iv) of this section, during the application of simulated ringing 
as listed in table I.
    (2) For individual equipment intended for operation on ground-start 
telephone facilities:
    (i) The maximum total dc current flowing between tip and ring 
conductors during the application of simulated ringing as listed in 
table I below, in milliamperes, divided by 0.6 milliamperes.
    (ii) Five times the impedance limitation listed in table I below 
divided by the minimum measured ac impedance, defined in paragraph 
(b)(2) of this section, during the application of simulated ringing as 
listed in table I.

The largest of the unitless quotients so formed, followed by the Ringing 
Type letter indicator representing the frequency range for which that 
number is valid, is the Ringer Equivalence. If Ringer Equivalence is to 
be stated for more than one Ringing Type, testing shall be performed at 
each frequency range to which Ringer Equivalence is to be determined in 
accordance with the above, and the largest resulting Ringer Equivalence 
number so determined will be associated with each Ringing Type letter 
designation for which it is valid.
    (e) Registered terminal equipment and registered protective 
circuitry shall have at least one ringer equivalence number shown on the 
registration label. Where options that will vary

[[Page 307]]

the ringer equivalence are involved, either each option that results in 
a ringer equivalence number greater than 0.1 and its corresponding 
Ringer Equivalence shall be listed on the registration label, or the 
largest ringer equivalence number that can result from such options 
shall be stated on the label. A trained, authorized agent of the Grantee 
may disconnect ringers, bridge ringers to another line, or execute 
options affecting ringer equivalence after the telephone company has 
been notified in accordance with Sec. 68.106.
    (f) All registered terminal equipment and registered protective 
circuitry which can affect on-hook impedance shall be assigned a Ringer 
Equivalence. The sum of all such ringer equivalences on a given 
telephone line or loop shall not exceed 5; in some cases, a system which 
has a total ringer equivalence of 5 or less may not be usable on a given 
telephone line or loop.
    (g) Ringing type Z equipment. Equipment which has on-hook impedance 
characteristics which do not conform to the requirements of this section 
may be conditionally registered, notwithstanding the requirements of 
this section, provided that it is labelled with a Ringing Type 
designation ``Z''. It should be noted that registration of equipment 
bearing the designation ``Z'' does not necessarily confer any right of 
connection to the telephone network under these rules; any equipment 
registered with the type Z designation may only be used with the consent 
of the local telephone company, provided that the local telephone 
company does not discriminate in its treatment of equipment bearing the 
type Z designation.
    (h) Limitations on PBX equipment with an off-premises interface and 
direct inward dialing (DID). PBX ringing supplies whose output appears 
on the off-premises interface leads shall not trip when connected to the 
following tip-to-ring impedance which terminates the off-premises 
station loop:

                                                                        
------------------------------------------------------------------------
                                                     ac impedance ohms  
                                                 -----------------------
              Ringing frequency Hz                 Class B,             
                                                     or C       Class A 
------------------------------------------------------------------------
                                                        7000        1400
20  plus-minus  3...............................        ----            
                                                         N              
                                                        5000        1000
30  plus-minus  3...............................        ----            
                                                         N              
------------------------------------------------------------------------
N--Number of ringer equivalences, as specified by the manufacturer,     
  which can be connected to the off-premises station loop.              

    (i) Limitations on individual equipment intended for operation with 
message register signaling channels:
    (1) Registered terminal equipment and registered protective 
circuitry shall conform to the following limitations in all operating 
states.
    (2) The dc resistance between each of the tip (MR) and ring (MR) 
conductors and ground shall be greater than 30 kilohms for voltages up 
to and including 200 volts.
    (j) Limitations on individual equipment ports with ringdown or 
inband signaling or voiceband metallic channels for connection to 
voiceband private line interfaces.
    (1) Registered terminal equipment and registered protective 
circuitry with 2-wire ports for ringdown, inband signaling or voiceband 
metallic channels shall provide a dc resistance between tip and ring 
conductors and between each of the tip and ring conductors and earth 
ground greater than 30 kilohms for all dc voltages up to and including 
200 volts.
    (2) Registered terminal equipment and registered protective 
circuitry with 4-wire ports for ringdown, inband signaling or voiceband 
metallic channels shall provide a dc resistance between each of the tip, 
ring, tip 1 and ring 1 conductors and earth ground greater than 30 
kilohms for all dc voltages up to and including 200 volts.
    (k) Registered terminal equipment and registered protective 
circuitry shall not by design leave the on-hook state by operations 
performed on tip and ring leads for any other purpose than to request 
service or answer an incoming call, except that terminal equipment which 
the user places in the off-hook state for the purpose of manually 
placing telephone numbers in internal memory for subsequent automatic or 
repertory dialing shall be registrable. Make-busy indications shall be 
transmitted by the use of make-

[[Page 308]]

busy leads only as defined in Secs. 68.3 and 68.200(j).

                                 Table I                                
------------------------------------------------------------------------
                 Range of compatible     Simulated ringing     Impedance
 Ringing type    ringing frequencies    voltage superimposed  limitation
                          Hz               56.5 volts dc        (ohms)  
------------------------------------------------------------------------
A.............  20 plus-minus 3......  40 to 130 volts rms..       1400 
                30 plus-minus 3......  40 to 130 volts rms..       1000 
B.............  15.3 to 68.0.........  40 to 150 volts rms..       1600 
C.............  15.3 to 17.4.........  54 to 120 volts rms..       1600 
D.............  19.3 to 20.7 \1\       54 to 120 volts rms..       1600 
                 (frequency-                                            
                 selective).                                            
E.............  24.3 to 25.7.........  54 to 120 volts rms..       1600 
F.............  29.3 to 30.7 \1\       54 to 120 volts rms..       1600 
                 (frequency-                                            
                 selective).                                            
G.............  32.6 to 34.0.........  54 to 130 volts rms..       1600 
H.............  39.2 to 40.9.........  62 to 130 volts rms..       1600 
J.............  41.0 to 43.0.........  62 to 130 volts rms..       1600 
K.............  49.0 to 51.0.........  62 to 140 volts rms..       1600 
L.............  52.9 to 55.1.........  62 to 140 volts rms..       1600 
M.............  58.8 to 61.2.........  68 to 150 volts rms..       1600 
N.............  65.4 to 68.0.........  68 to 150 volts rms..       1600 
P.............  15.3 to 34.0.........  54 to 130 volts rms..       1600 
Q.............  20 plus-minus 3......  40 to 130 volts rms..       1400 
------------------------------------------------------------------------
\1\ Note: Requirements at these frequencies, which are identical to Type
  A frequencies, are not consistent with the Type A requirements;       
  equipment intended for use both on Type A facilities and facilities   
  using frequency-selective ringing must comply with the requirements on
  Types A, D and F independently.                                       


[ 45 FR 20853 , Mar. 31, 1980, as amended at  45 FR 61632 , Sept. 17, 1980; 
 45 FR 79486 , Dec. 1, 1980;  46 FR 40192 , Aug. 7, 1981;  48 FR 34044 , July 
27, 1983;  51 FR 950 , Jan. 9, 1986;  51 FR 28237 , Aug. 6, 1986;  61 FR 42394 , Aug. 15, 1996;  61 FR 47434 , Sept. 9, 1996]


Goto Section: 68.310 | 68.314

Goto Year: 1996 | 1998
CiteFind - See documents on FCC website that cite this rule

Want to support this service?
Thanks!

Report errors in this rule. Since these rules are converted to HTML by machine, it's possible errors have been made. Please help us improve these rules by clicking the Report FCC Rule Errors link to report an error.
hallikainen.com
Helping make public information public