Goto Section: 68.214 | 68.218 | Table of Contents
FCC 68.215
Revised as of October 1, 2020
Goto Year:2019 |
2021
§ 68.215 Installation of other than "fully protected" system premises wiring
that serves more than four subscriber access lines.
(a) Types of wiring authorized--(1) Between equipment entities.
Unprotected premises wiring, and protected premises wiring requiring
acceptance testing for imbalance, may be used to connect
separately-housed equipment entities to one another.
(2) Between an equipment entity and the public switched telephone
network interface(s). Fully-protected premises wiring shall be used to
connect equipment entities to the public switched telephone network
interface unless the provider of wireline telecommunications is
unwilling or unable to locate the interface within 7.6 meters (25 feet)
of the equipment entity on reasonable request. In any such case, other
than fully-protected premises wiring may be used if otherwise in
accordance with these rules.
(3) Hardware protection as part of the facilities of the provider of
wireline telecommunications. In any case where the carrier chooses to
provide (and the customer chooses to accept, except as authorized under
paragraph (g) of this section), hardware protection on the network side
of the interface(s), the presence of such hardware protection will
affect the classification of premises wiring for the purposes of
§ 68.215, as appropriate.
(b) Installation personnel. Operations associated with the
installation, connection, reconfiguration and removal (other than final
removal of the entire premises communications system) of other than
fully-protected premises wiring shall be performed under the
supervision and control of a supervisor, as defined in paragraph (c) of
this section. The supervisor and installer may be the same person.
(c) Supervision. Operations by installation personnel shall be
performed under the responsible supervision and control of a person
who:
(1) Has had at least six months of on-the-job experience in the
installation of telephone terminal equipment or of wiring used with
such equipment;
(2) Has been trained by the registrant of the equipment to which the
wiring is to be connected in the proper performance of any operations
by installation personnel which could affect that equipment's continued
compliance with these rules;
(3) Has received written authority from the registrant to assure that
the operations by installation personnel will be performed in such a
manner as to comply with these rules.
(4) Or, in lieu of paragraphs (c) (1) through (3) of this section, is a
licensed professional engineer in the jurisdiction in which the
installation is performed.
(d) Workmanship and material requirements--(1) General. Wiring shall be
installed so as to assure that there is adequate insulation of
telephone wiring from commercial power wiring and grounded surfaces.
Wiring is required to be sheathed in an insulating jacket in addition
to the insulation enclosing individual conductors (see below) unless
located in an equipment enclosure or in an equipment room with
restricted access; it shall be assured that this physical and
electrical protection is not damaged or abraded during placement of the
wiring. Any intentional removal of wiring insulation (or a sheath) for
connections or splices shall be accomplished by removing the minimum
amount of insulation necessary to make the connection or splice, and
insulation equivalent to that provided by the wire and its sheath shall
be suitably restored, either by placement of the splices or connections
in an appropriate enclosure, or equipment rooms with restricted access,
or by using adequately-insulated connectors or splicing means.
(2) Wire. Insulated conductors shall have a jacket or sheath with a
1500 volt rms minimum breakdown rating, except when located in an
equipment enclosure or an equipment room with restricted access. This
rating shall be established by covering the jacket or sheath with at
least 15 cm (6 in) (measured linearly on the cable) of conductive foil,
and establishing a potential difference between the foil and all of the
individual conductors connected together, such potential difference
gradually increased over a 30 second time period to 1500 volts rms, 60
Hertz, then applied continuously for one minute. At no time during this
90 second time interval shall the current between these points exceed
10 milliamperes peak.
(3) Places where the jacket or sheath has been removed. Any point where
the jacket or sheath has been removed (or is not required) shall be
accessible for inspection. If such points are concealed, they shall be
accessible without disturbing permanent building finish (e.g., by
removing a cover).
(4) Building and electrical codes. All building and electrical codes
applicable in the jurisdiction to telephone wiring shall be complied
with. If there are no such codes applicable to telephone wiring,
Article 800 of the 1978 National Electrical Code, entitled
Communications Systems, and other sections of that Code incorporated
therein by reference shall be complied with.
(5) Limitations on electrical signals. Only signal sources that emanate
from the provider of wireline telecommunications central office, or
that are generated in equipment at the customer's premises and are
"non-hazardous voltage sources" as defined in the technical criteria
published by the Administrative Council for Terminal Attachments, may
be routed in premises telephone wiring, except for voltages for network
control signaling and supervision that are consistent with standards
employed by the provider of wireline telecommunications. Current on
individual wiring conductors shall be limited to values which do not
cause an excessive temperature rise, with due regard to insulation
materials and ambient temperatures. The following table assumes a 45 °C
temperature rise for wire sizes 22 AWG or larger, and a 40 °C rise for
wire sizes smaller than 22 AWG, for poly-vinyl chloride insulating
materials, and should be regarded as establishing maximum values to be
derated accordingly in specific installations where ambient
temperatures are in excess of 25 °C:
Maximum Continuous Current Capacity of PVC Insulated Copper Wire,
Confined
Wire size, AWG Circular mils Maximum current, amperes
32 63.2 0.32
30 100.5 0.52
28 159.8 0.83
26 254.1 1.3
24 404.0 2.1
22 642.4 5.0
20 1022 7.5
18 1624 10
Note: The total current in all conductors of multiple conductor cables
may not exceed 20% of the sum of the individual ratings of all such
conductors.
(6) Physical protection. In addition to the general requirements that
wiring insulation be adequate and not damaged during placement of the
wiring, wiring shall be protected from adverse effects of weather and
the environment in which it is used. Where wiring is attached to
building finish surfaces (surface wiring), it shall be suitably
supported by means which do not affect the integrity of the wiring
insulation.
(e) Documentation requirements. A notarized affidavit and one copy
thereof shall be prepared by the installation supervisor in advance of
each operation associated with the installation, connection,
reconfiguration and removal of other than fully-protected premises
wiring (except when accomplished functionally using a cross-connect
panel), except when involved with removal of the entire premises
communications system using such wiring. This affidavit and its copy
shall contain the following information:
(1) The responsible supervisor's full name, business address and
business telephone number.
(2) The name of the registrant(s) (or manufacturer(s), if grandfathered
equipment is involved) of any equipment to be used electrically between
the wiring and the telephone network interface, which does not contain
inherent protection against hazardous voltages and longitudinal
imbalance.
(3) A statement as to whether the supervisor complies with § 68.215(c).
Training and authority under § 68.215(c)(2)-(3) is required from the
registrant (or manufacturer, if grandfathered equipment is involved) of
the first piece of equipment electrically connected to the telephone
network interface, other than passive equipments such as extensions,
cross-connect panels, or adapters. In general, this would be the
registrant (or manufacturer) of a system's common equipment.
(4) The date(s) when placement and connection of the wiring will take
place.
(5) The business affiliation of the installation personnel.
(6) Identification of specific national and local codes which will be
adhered to.
(7) The manufacturer(s); a brief description of the wire which will be
used (model number or type); its conformance with recognized standards
for wire if any (e.g., Underwriters Laboratories listing, Rural
Electrification Administration listing, "KS-" specification, etc.); and
a general description of the attachment of the wiring to the structure
(e.g., run in conduit or ducts exclusively devoted to telephone wiring,
"fished" through walls, surface attachment, etc.).
(8) The date when acceptance testing for imbalance will take place.
(9) The supervisor's signature. The notarized original shall be
submitted to the provider of wireline telecommunications at least ten
calendar days in advance of the placement and connection of the wiring.
This time period may be changed by agreement of the provider of
wireline telecommunications and the supervisor. The copy shall be
maintained at the premises, available for inspection, so long as the
wiring is used for telephone service.
(f) Acceptance testing for imbalance. Each telephone network interface
that is connected directly or indirectly to other than fully-protected
premises wiring shall be subjected to the acceptance test procedures
specified in this section whenever an operation associated with the
installation, connection, reconfiguration or removal of this wiring
(other than final removal) has been performed.
(1) Test procedure for two-way or outgoing lines or loops. A telephone
instrument may be associated directly or indirectly with the line or
loop to perform this test if one is not ordinarily available to it:
(i) Lift the handset of the telephone instrument to create the off-hook
state on the line or loop under test.
(ii) Listen for noise. Confirm that there is neither audible hum nor
excessive noise.
(iii) Listen for dial tone. Confirm that dial tone is present.
(iv) Break dial tone by dialing a digit. Confirm that dial tone is
broken as a result of dialing.
(v) With dial tone broken, listen for audible hum or excessive noise.
Confirm that there is neither audible hum nor excessive noise.
(2) Test procedure for incoming-only (non-originating) lines or loops.
A telephone instrument may be associated directly or indirectly with
the line or loop to perform this test if one is not ordinarily
available to it:
(i) Terminate the line or loop under test in a telephone instrument in
the on-hook state.
(ii) Dial the number of the line or loop under test from another
station, blocking as necessary other lines or loops to cause the line
or loop under test to be reached.
(iii) On receipt of ringing on the line or loop under test, lift the
handset of the telephone instrument to create the off-hook state on
that line or loop.
(iv) Listen for audible hum or excessive noise. Confirm that there is
neither audible hum nor excessive noise.
(3) Failure of acceptance test procedures. Absence of dial tone before
dialing, inability to break dial tone, or presence of audible hum or
excessive noise (or any combination of these conditions) during test of
two-way or outgoing lines or loops indicates failure. Inability to
receive ringing, inability to break ringing by going off-hook, or
presence of audible hum or excessive noise (or any combination of these
conditions) during test of incoming-only lines or loops indicates
failure. Upon any such failure, the failing equipment or portion of the
premises communications system shall be disconnected from the network
interface, and may not be reconnected until the cause of the failure
has been isolated or removed. Any previously tested lines or loops
shall be retested if they were in any way involved in the isolation and
removal of the cause of the failure.
(4) Monitoring or participation in acceptance testing by the provider
of wireline telecommunications. The provider of wireline
telecommunications may monitor or participate in the acceptance testing
required under this section, in accordance with § 68.215(g) of this
part, from its central office test desk or otherwise.
(g) Extraordinary procedures. The provider of wireline communications
is hereby authorized to limit the subscriber's right of connecting
approved terminal equipment or protective circuitry with other than
fully-protected premises wiring, but solely in accordance with this
paragraph and § 68.108 of these rules.
(1)(i) Conditions that may invoke these procedures. The extraordinary
procedures authorized herein may only be invoked where one or more of
the following conditions is present:
(A) Information provided in the supervisor's affidavit gives reason to
believe that a violation of part 68 of the FCC's rules is likely.
(B) A failure has occurred during acceptance testing for imbalance.
(C) Harm has occurred, and there is reason to believe that this harm
was a result of wiring operations performed under this section.
(ii) The extraordinary procedures authorized in the following
subsections shall not be used so as to discriminate between
installations by provider of wireline telecommunications personnel and
installations by others. In general, this requires that any charges for
these procedures be levied in accordance with, or analogous to, the
"maintenance of service" tariff provisions: If the installation proves
satisfactory, no charge should be levied.
(2) Monitoring or participation in acceptance testing for imbalance.
Notwithstanding the previous sub-section, the provider of wireline
telecommunications may monitor or participate in acceptance testing for
imbalance at the time of the initial installation of wiring in the
absence of the conditions listed therein; at any other time, on or more
of the listed conditions shall be present. Such monitoring or
participation in acceptance testing should be performed from the
central office test desk where possible to minimize costs.
(3) Inspection. Subject to paragraph (g)(1) of this section, the
provider of wireline telecommunications may inspect wiring installed
pursuant to this section, and all of the splicing and connection points
required to be accessible by § 68.215(d)(3) to determine compliance with
this section. The user or installation supervisor shall either
authorize the provider of wireline telecommunications to render the
splicing and inspection points visible (e.g., by removing covers), or
perform this action prior to the inspection. To minimize disruption of
the premises communications system, the right of inspecting is limited
as follows:
(i) During initial installation of wiring:
(A) The provider of wireline telecommunications may require withdrawal
of up to 5 percent (measured linearly) of wiring run concealed in
ducts, conduit or wall spaces, to determine conformance of the wiring
to the information furnished in the affidavit.
(B) In the course of any such inspection, the provider of wireline
telecommunications shall have the right to inspect documentation
required to be maintained at the premises under § 68.215(e).
(ii) After failure of acceptance testing or after harm has resulted
from installed wiring: The provider of wireline telecommunications may
require withdrawal of all wiring run concealed in ducts, conduit or
wall spaces which reasonably could have caused the failure or harm, to
determine conformance of the wiring to the information furnished in the
affidavit.
(iii) In the course of any such inspection, the provider of wireline
telecommunications shall have the right to inspect documentation
required to be maintained at the premises under § 68.215(e).
(4) Requiring the use of protective apparatus. In the event that any of
the conditions listed in paragraph (g)(1) of this section, arises, and
is not permanently remedied within a reasonable time period, the
provider of wireline telecommunications may require the use of
protective apparatus that either protects solely against hazardous
voltages, or that protects both against hazardous voltages and
imbalance. Such apparatus may be furnished either by the provider of
wireline telecommunications or by the customer. This right is in
addition to the rights of the provider of wireline telecommunications
under § 68.108.
(5) Notice of the right to bring a complaint. In any case where the
provider of wireline telecommunications invokes the extraordinary
procedures of § 68.215(g), it shall afford the customer the opportunity
to correct the situation that gave rise to invoking these procedures,
and inform the customer of the right to bring a complaint to the
Commission pursuant to the procedures set forth in subpart E of this
part. On complaint, the Commission reserves the right to perform any of
the inspections authorized under this section, and to require the
performance of acceptance tests.
(h) Limitations on the foregoing if protected wiring requiring
acceptance testing is used. If protected wiring is used which required
acceptance testing, the requirements in the foregoing paragraphs of
§ 68.215 are hereby limited, as follows:
(1) Supervision. Section 68.215(c)(2)-(3) are hereby waived. The
supervisor is only required to have had at least six months of
on-the-job experience in the installation of telephone terminal
equipment or of wiring used with such equipment.
(2) Extraordinary procedures. Section 68.215(g)(3) is hereby limited to
allow for inspection of exposed wiring and connection and splicing
points, but not for requiring the withdrawal of wiring from wiring run
concealed in ducts, conduit or wall spaces unless actual harm has
occurred, or a failure of acceptance testing has not been corrected
within a reasonable time. In addition, § 68.215(g)(4) is hereby waived.
[ 43 FR 16499 , Apr. 19, 1978, as amended at 44 FR 7958 , Feb. 8, 1979; 47 FR 37896 , Aug. 27, 1982; 49 FR 21735 , May 23, 1984; 58 FR 44907 , Aug.
25, 1993; 66 FR 7584 , Jan. 24, 2001]
Goto Section: 68.214 | 68.218
Goto Year: 2019 |
2021
CiteFind - See documents on FCC website that
cite this rule
Want to support this service?
Thanks!
Report errors in
this rule. Since these rules are converted to HTML by machine, it's possible errors have been made. Please
help us improve these rules by clicking the Report FCC Rule Errors link to report an error.
hallikainen.com
Helping make public information public